- One Model ERICORE
The goal was to improve on the performance of E2, yet
keep size benefits of E1
- Insulation spec’d at LDPE or XLPE, minimum rating of
33 kV, 50 kV/mm.
- Cable to be triple extruded – extruded
semiconductive layers to be 0.5 mm
- 55mm sq core
- Semi-conductive outer sheath 100ohm.mm
- Insulation Layer 1.8mm – improved tolerance
Testing
Independent Test results at TRL Labs in Melbourne
Result => breakdown at 310kV @ 1.2/50us
Recall E1 and E2, same tests breakdown at
180-190kV 1.2/50us
New
Termination Kit
- Easier to apply
- Higher Rating